168

H9 ASD Installation and Operation Manual

S-Pattern Acceleration Lower Limit Adjustment

Program

Special

Accel/Decel Special

During an S-Pattern 1 or 2 sequence, this parameter settings modifies the
acceleration rate for the lower part of the acceleration curve by the percentage
set here.

This function is commonly used with transportation and lifting applications.

See parameter

F502 on pg. 165

for more information on this setting.

Direct Access Number — F506

Parameter Type — Numerical

Factory Default — 10

Changeable During Run — Yes

Minimum — 0

Maximum — 50

Units — %

S-Pattern Acceleration Upper Limit Adjustment

Program

Special

Accel/Decel Special

During an S-Pattern 1 or 2 sequence, this parameter settings modifies the
acceleration rate for the upper part of the acceleration curve by the percentage
set here.

This function is commonly used with transportation and lifting applications.

See parameter

F502 on pg. 165

for more information on this setting.

Direct Access Number — F507

Parameter Type — Numerical

Factory Default — 10

Changeable During Run — Yes

Minimum — 0

Maximum — 50

Units — %

S-Pattern Deceleration Lower Limit Adjustment

Program

Special

Accel/Decel Special

During an S-Pattern 1 or 2 sequence, this parameter settings modifies the
deceleration rate for the lower part of the deceleration curve by the percentage
set here.

This function is commonly used with transportation and lifting applications.

See parameter

F502 on pg. 165

for more information on this setting.

Direct Access Number — F508

Parameter Type — Numerical

Factory Default — 10

Changeable During Run — Yes

Minimum — 0

Maximum — 50

Units — %

S-Pattern Deceleration Upper Limit Adjustment

Program

Special

Accel/Decel Special

During an S-Pattern 1 or 2 sequence, this parameter settings modifies the
deceleration rate for the upper part of the deceleration curve by the percentage
set here.

This function is commonly used with transportation and lifting applications.

See parameter

F502 on pg. 165

for more information on this setting.

Direct Access Number — F509

Parameter Type — Numerical

Factory Default — 10

Changeable During Run — Yes

Minimum — 0

Maximum — 50

Units — %

Acceleration Time 3

Program

Special

Accel/Decel #1 – #4 Settings

This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the Maximum Frequency for the #3 Acceleration profile. The
Accel/Decel pattern may be set using

F502

. The minimum Accel/Decel time

may be set using

F508

.

Note:

An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel
, Stall, and Ridethrough settings may lengthen the
acceleration times.

Direct Access Number — F510

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

F506

F510