7 on pg. 19 – Toshiba H9 User Manual

Page 27

Advertising
background image

H9 ASD Installation and Operation Manual

19

Figure 4. The Grounding Capacitor Switch is

used on typeforms 230-volt 0.5 HP to 10 HP

and the 25 and 30 HP/460-volt 1.0 HP to

250 HP.

The value may be set to Maximum (default

setting) or to zero by pushing or pulling the

switch actuator, respectively.

Figure 5. The Grounding Capacitor

Switch is used on typeforms 230-volt

15 HP to 20 HP and the 40 HP to 60

HP/460-volt 30 HP to 100 HP.

The value may be set to Large

(default setting) or Small by pushing

or pulling the switch actuator,

respectively.

Figure 6. The Grounding Capacitor Bar is

used on typeforms 230-volt 75 HP and the

100 HP/460-volt 125 HP and the 150 HP.

The value may set to Large or Small (default

setting) by connecting or disconnecting the

switching bar, respectively.

Figure 7. The Grounding Capacitor Screw is

used on typeforms 460-volt 175 HP and

above.

The value may set to Large or Small (default

setting) by placing the screw in the A position

or by placing the screw in the B position,

respectively.