F264 on pg. 128, F264 – Toshiba H9 User Manual

Page 136

Advertising
background image

128

H9 ASD Installation and Operation Manual

UP/DOWN Frequency (up) Response Time

No Path — Direct Access Only

This parameter functions in conjunction with the parameter settings of

F265

,

F266

,

F267

,

F268

, and

F269

. The purpose of these settings is to setup the ASD

to allow an externally-supplied discrete input signal to control the output
frequency of the ASD.

This method uses the discrete input terminal settings UP/DOWN Frequency
(up)
and UP/DOWN Frequency (down) to change the ASD speed. Activation
of either terminal increases or decreases the output frequency at the Accel 1 or
Decel 1 rates, respectively.

Depending on the Delay setting, the UP/DOWN Frequency (up/down)
terminal may perform 1) the increase/decrease function for the duration of
activation or 2) the UP/DOWN Frequency (up/down) terminal may act as a
momentary contact that loads a new commanded frequency upon activation.

In either case, to activate-and-hold will continue the up or down function until
reaching the Upper Limit Frequency or the Lower Limit Frequency,
respectively. At which point further activation will be ignored.

See

Figure 29 on pg. 130

for more information on the UP/DOWN Frequency

function.

Setup Requirements

F003

Selects the Command control source; set to Terminal Block.

F004

Selects the Frequency Control Mode 1 control source; set to

UP/DOWN Frequency.

F207

Selects the Frequency Control Mode 2 control source: set to

UP/DOWN Frequency if used.

Set one unused discrete input terminal to UP/DOWN Frequency (up) and
one unused discrete input terminal to UP/DOWN Frequency (down).

F264

Sets the system-response delay to the initial activation of the discrete

input terminal UP/DOWN Frequency (up). Also sets the response delay of
subsequent terminal activations of the UP/DOWN Frequency (up) terminal
during an activate-and-hold.

F265

Sets the frequency increase amount for each activation of the UP/

DOWN Frequency (up) terminal activation. The rate of the frequency
increase is set at Acceleration Time 1 (

F009

).

F266

Sets the system-response delay to the initial activation of the discrete

input terminal UP/DOWN Frequency (down). Also sets the activation delay
of subsequent terminal activations of the UP/DOWN Frequency (down)
terminal during an activate-and-hold.

F267

Sets the frequency decrease amount for each activation of the UP/

DOWN Frequency (down) terminal activation. The rate of the frequency
decrease is set at Deceleration Time 1 (

F010

).

F268

At power up or after a reset, this parameter setting is used to provide

a starting frequency for the UP/DOWN Frequency function.

F269

At power down while running, and when enabled, this parameter

writes the running frequency into the

F268

location and, upon a system

restart, uses this setting as the startup frequency.

Provide a Run command (F or R). The motor will run at the

F268

setting.

Direct Access Number — F264

Parameter Type — Numerical

Factory Default — 0.1

Changeable During Run — Yes

Minimum — 0.0

Maximum — 10.0

Units — Seconds

Up/Down Frequency (up) Mode

Up/Down Frequency (down) Mode

F264