122

H9 ASD Installation and Operation Manual

PG Input Point 1 Setting

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the PG input terminal of the
option board when a shaft-mounted encoder is used as the control input while
operating in the Speed Control mode.

Note:

See Instruction Manual P/N 58687 for more information on the
PG Option Board.

PG Input Speed Control Setup

Perform the following setup to allow the system to receive Speed control input
at the PG input terminal:

• Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Frequency Mode

1

Pulse Input (option).

• Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode

Selection

⇒ (any setting).

• Provide a Run command (F and/or R).

Speed Control

Perform the following setup to allow the system to perform Speed control from
the PG input terminals:

• Set PG Point 1 Frequency (

F235

).

• Set the PG input value (

F234

) that represents PG Point 1 Frequency.

• Set PG Point 2 Frequency (

F237

).

• Set the PG input value (

F236

) that represents PG Point 2 Frequency.

Once set, as the PG input pulse count rate changes, the output frequency of the
drive will vary in accordance with the above settings.

This parameter sets the PG input pulse count that represents Reference
Setpoint #1 (frequency)
. The range of values for this parameter is 0% to 100%
of the PG input pulse count range.

Note:

Further application-specific PG settings may be performed from
the following path: Program

Feedback PG Settings.

Direct Access Number — F234

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — 0

Maximum — 100.0

Units — %

Frequency Settings

PG Input Point 1 Frequency

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the speed of the PG input terminals when the PG
terminal is used as the control input.

This parameter sets PG Point 1 Frequency and is the frequency that is
associated with the setting of PG Point 1 Setting.

See PG Point 1 Setting for further information on this setting.

Direct Access Number — F235

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

F234

F235