F616, F617, F618 – Toshiba H9 User Manual

Page 194: F619, F620, F621

Advertising
background image

186

H9 ASD Installation and Operation Manual

Overtorque Detection Level (Positive Torque)

Program

Protection

Overtorque Parameters

This parameter sets the torque threshold level that is used as a setpoint for
overtorque tripping during positive torque. This setting is a percentage of the
maximum rated torque of the drive.

This function is enabled at

F615

.

Direct Access Number — F616

Parameter Type — Numerical

Factory Default — 150.00

Changeable During Run — No

Minimum — 0.00

Maximum — 250.00

Units — %

Overtorque Detection Level (Negative Torque)

Program

Protection

Overtorque Parameters

This parameter sets the torque threshold level that is used as a setpoint for
overtorque tripping during negative torque (regen). This setting is a percentage
of the maximum rated torque of the drive.

This function is enabled at

F615

.

Direct Access Number — F617

Parameter Type — Numerical

Factory Default — 150.00

Changeable During Run — No

Minimum — 0.00

Maximum — 250.00

Units — %

Overtorque Detection Time

Program

Protection

Overtorque Parameters

This parameter sets the amount of time that the overtorque condition may
exceed the tripping threshold level set at

F616 and F617

before a trip occurs.

This function is enabled at

F615

.

Direct Access Number — F618

Parameter Type — Numerical

Factory Default — 0.50

Changeable During Run — No

Minimum — 0.00

Maximum — 10.0

Units — Seconds

Overtorque Detection Hysteresis

Program

Protection

Overtorque Parameters

During a momentary overtorque condition, this parameter provides a torque
threshold level to which the overtorque condition must return within the time
setting of

F618

or an Overtorque Trip will be incurred.

Direct Access Number — F619

Parameter Type — Numerical

Factory Default — 10.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 100.00

Units — %

Cooling Fan Control

Program

Protection

Special Protection Parameters

This parameter sets the cooling fan run-time command.

Settings:

0 — Automatic
1 — Always On

Direct Access Number — F620

Parameter Type — Selection List

Factory Default — Automatic

Changeable During Run — Yes

Cumulative Operation Time Alarm

Program

Protection

Special Protection Parameters

This parameter sets a run-time value that, once exceeded, closes a discrete
output contact. The output signal may be used to control external equipment or
used to engage a brake.

Associate the Total-operation-hours Alarm setting of

Table 8 on pg. 241

to a

discrete output contactor.

Note:

The time displayed is 1/10th of the actual time (0.1 hr. = 1.0 hr.).

Direct Access Number — F621

Parameter Type — Numerical

Factory Default — 610.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 999.9

Units — Hours (X 10)