H9 ASD Installation and Operation Manual

Overload Reduction Starting Frequency

Program

Protection

Overload

This parameter is primarily used with V/f motors. It is used to reduce the
starting frequency at which the Overload Reduction function begins and is
useful during extremely low-speed motor operation.

During very low-speed operation the cooling efficiency of the motor decreases.
Lowering the start frequency of the Overload Reduction function aides in
minimizing the generated heat and precluding an Overload trip.

This function is useful in loads such as fans, pumps, and blowers that have the
square reduction torque characteristic.

Set parameter

F607

to the desired Overload Time Limit.

Direct Access Number — F606

Parameter Type — Numerical

Factory Default — 6.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 30.00

Units — Hz

Motor 150% Overload Time Limit

Program

Protection

Overload

This parameter establishes a time that the motor may operate at 150% of its
rated current before tripping. This setting applies the time/150% reference to
the individual settings of each motor (e.g., this setting references 150% of the

F600

setting for the #1 motor).

The unit will trip sooner than the time entered here if the overload is greater
than 150%.

Direct Access Number — F607

Parameter Type — Numerical

Factory Default — 300

Changeable During Run — Yes

Minimum — 10

Maximum — 2400

Units — Seconds

ASD Input Phase Failure Detection

Program

Protection

Phase Loss

This parameter enables the 3-phase input power phase loss detection feature. A
loss of either input phase (R, S, or T) results in a trip.

Settings:

0 — Disabled
1 — Enabled

Direct Access Number — F608

Parameter Type — Selection List

Factory Default — Enabled

Changeable During Run — No

Low Current Detection Current Hysteresis Width

Program

Protection

Low Current Settings

During a momentary low-current condition, this parameter provides a current
threshold level to which the low-current condition must return within the time
setting of

F612

or a Low Current Trip will be incurred.

Direct Access Number — F609

Parameter Type — Numerical

Factory Default — 10

Changeable During Run — Yes

Minimum — 1

Maximum — 20

Units — %

Low Current Trip

Program

Protection

Low Current Settings

This parameter Enables/Disables the low-current trip feature.

When enabled, the drive will trip on a low-current fault if the output current of
the drive falls below the level defined at

F611

and remains there for the time set

at

F612

.

Settings:

0 — Disabled
1 — Enabled

Direct Access Number — F610

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No