Short circuit protection recommendations, Table 22 on pg. 267, For typ – Toshiba H9 User Manual

Page 275

Advertising
background image

H9 ASD Installation and Operation Manual

267

Short Circuit Protection Recommendations

Table 22. 230/240 and 400/480-Volt ASD recommended circuit breaker selection.

Model Number

VT130H9U

HP

Continuous Output Current

(Amps)

Circuit Breaker Part Number

2035

3.0

10.0

HLL36025

2055

5.0

17.5

HLL36025

2080

7.5

27.5

HLL36040

2110

10

33.0

HLL36050

2160

15

54.0

HLL36070

2220

20

66.0

HLL36090

2270

25

76.0

HLL36100

2330

30

90.0

HLL36100

2400

40

120

HLL36125

2500

50

152

HLL36150

2600

60

176

JLL36200

2750

75

221

Contact Toshiba Customer Service

210K

100

285

212K

125

365

4055

5

10.5

HLL36025

4080

7.5

14.3

HLL36040

4110

10

17.6

HLL36050

4160

15

27.7

HLL36070

4220

20

33.0

HLL36090

4270

25

41.0

HLL36100

4330

30

48.0

HLL36100

4400

40

66.0

HLL36125

4500

50

79.0

HLL36150

4600

60

94.0

JLL36200

4750

75

116

JLL36225

410K

100

160

JLL36250

412K

125

179

LIL36300

415K

150

215

LIL36300

420K

200

259

LIL36400

425K

250

314

LIL36400

430K

300

387

Contact Toshiba Customer Service

435K

350

434

440K

400

495

Advertising