F631 – Toshiba H9 User Manual
Page 197
H9 ASD Installation and Operation Manual
189
ASD Overload
Program
⇒
Protection
⇒
Overload
This parameter is used to protect the ASD from an overcurrent condition. The
standard overload rating of the H9 ASD is 150% operation for 60 seconds.
This setting allows for the overload protection to be switched from the standard
overload detection means (Thermal Detection and Overload) to thermal
detection only.
Settings:
0 — Thermal Detection + Overload
1 — Thermal Detection Only
The Thermal Detection Only selection is used when multiple devices are
installed horizontally as described on
. If the installation provides for no
space in between the adjacent devices the ASDs must be derated as described in
Direct Access Number — F631
Parameter Type — Selection List
Factory Default — Thermal Detection +
Overload
Changeable During Run — No