F003, F004 – Toshiba H9 User Manual

Page 85

Advertising
background image

H9 ASD Installation and Operation Manual

77

Command Mode

Program

Fundamental

Standard Mode Selection

The Command Mode Selection establishes the source of the command input
for the ASD. Command inputs include Run, Stop, Forward, etc. The Override
feature may supersede the Command Mode Selection setting (see

Command

Mode and Frequency Mode Control on pg. 36

).

Settings:

0 — Terminal Block
1 — Not Used
2 — EOI Keypad
3 — RS485
4 — Communication Option Board

Direct Access Number — F003

Parameter Type — Selection List

Factory Default — Terminal Block

Changeable During Run — No

Frequency Mode 1

Program

Fundamental

Standard Mode Selection

The Frequency Mode 1 setting establishes the source of the frequency-control
input for the ASD. The Frequency Mode 2 setting or the Override feature may
supersede the Frequency Mode 1 setting (see

Command Mode and Frequency

Mode Control on pg. 36

and

F200

for more information on this setting).

Note:

Only Bolded items from the Settings list below may be placed in
the Override mode. See the section titled

Command Mode and

Frequency Mode Control on pg. 36

for more information on the

Override feature.

Settings:

1 — V/I
2 — RR
3 — RX
5 — EOI Keypad
6 — RS485
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency
11 — Pulse Input (option)
12 — Pulse Input (motor CPU)
13 — Binary/BCD Input (option)

Direct Access Number — F004

Parameter Type — Selection List

Factory Default — RR

Changeable During Run — No

F003

F004

Advertising