Terminal selection descriptions – Toshiba H9 User Manual

Page 245

Advertising
background image

H9 ASD Installation and Operation Manual

237

32

33

Torque Limit Switching 1/Torque Limit Switching 2

— Activating combinations of discrete input terminals

Torque Limit Switching 1 and 2 allow for the selection of a torque limit switching profile as listed below.

34

35

36

37

PID Off

— Turns off PID control.

38

39

Pattern Operation Group 1

— Initiates the Pattern #1 Pattern Run.

40

41

Pattern Operation Group 2

— Initiates the Pattern #2 Pattern Run.

42

43

Pattern Operation Continuation

— Initiates a continuation of the last Pattern Run from its stopping point.

44

45

Pattern Operation Trigger

— Initiates the first Preset Speed of a Pattern Run and initiates each subsequent

enabled Preset Speed with continued activations.

46

47

External Over-heat

— Causes an Over-Heat Trip (OH).

48

49

Local Priority

(cancels serial priority) — Overrides any serial control and returns the Command and Frequency

control to the settings of

F003

and

F004

.

50

51

Hold

(3-wire stop) — Decelerates the motor to a stop.

52

53

PID Differentiation/Integration Clear

— Clears the PID value.

54

55

PID Forward/Reverse Switching

— Toggles the gradient characteristic of the feedback response of the V/I

terminal during PID-controlled operation.

56

57

Forced Continuous Run

— Ignore PID control settings for the duration of activation.

58

59

Specified Speed

Operation — Runs speed as commanded by the Frequency Mode setting.

60

61

Dwell Signal

— Used in conjunction with the Acceleration/Deceleration Suspend function (

F349

) — suspends the

Accel/Decel function for the duration of the activation.

62

63

Power Failure Synchronized Signal —

Activates the Synchronized Accel/Decel function of the Regenerative

Power Ridethrough feature. See

F302

for more information on this terminal setting.

64

65

My Function Run

— Activates the configured My Function feature. See

F977

for more information on this

parameter.

66

67

Autotuning Signal

— Initiates the Autotune function. Set

F400

to Autotuning by Input Terminal Signal.

68

69

Speed Gain Switching

— Toggles the ASD operating mode from and to Speed Control and Torque Control.

Speed Control operation references parameter settings

F460

and

F461

. Torque Control operation references

parameter settings

F462

and

F463

.

70

71

Servo Lock

— Holds the motor at 0 Hz until a Run command is received.

72

73

Simple Positioning

— While operating in the Positioning Control mode, activation initiates the Stop command.

See

F381

for more information on this terminal setting.

74

75

kWH Display Clear

— Clears the kWH meter display.

76

77

Trace Back Trigger

— Initiates the data Read/Store function of the Trace Selection parameter. See

F740

for more

information on this feature.

78

79

Light-Load High-Speed Disable

— Terminates the Light-load High-speed operation.

Note:

NO/NC = Normally Open/Normally Closed.

Table 5. Discrete Input Terminal assignment selections and descriptions.

Sel. No.

Terminal Selection Descriptions

NO NC

Torque Limit

Switching Terminal

Torque Limit Selection

#1

#2

0

0

1

0

1

2

1

0

3

1

1

4

1 = Terminal Activated

The 1–4 settings of the torque limit switching
selections are performed at parameters

F440

F449

.