Led display lcd display possible causes – Toshiba H9 User Manual

Page 262

Advertising
background image

254

H9 ASD Installation and Operation Manual

OL1

ASD Overload

• Acceleration time is too short.

• DC Injection current is too high.

• Improper V/f setting.

• Motor running during restart.

• ASD or the motor is improperly matched to the application.

OL2

Motor Overload

• Improper V/f setting.

• Motor is locked.

• Continuous operation at low speed.

• Load requirement exceeds ability of the motor.

• Startup frequency setting adjustment required.

OLR

Dynamic Braking
Resistor Overload

• Deceleration time is too short.

• DBR setting adjustment required.

• Overvoltage Stall setting adjustment required.

OP1

Overvoltage During
Acceleration

• Motor running during restart.

OP2

Overvoltage During
Deceleration

• Deceleration time is too short.

• DBR value is too high.

• DBR required (DBR setup required).

• Stall protection is disabled.

• 3-phase input voltage is out of specification.

• Input reactance required.

OP3

Overvoltage During
Run

• Load fluctuations.

• 3-Phase input voltage out of specification.

• DBR required (DBR setup required).

OT

Overtorque

• A torque requirement by the load in excess of the setting of

F616

or

F617

for

a time longer than the setting of

F618

.

• The ASD is improperly matched to the application.

• The load is obstructed.

SOUT

Step-Out
(for PM Motor Only)

• Motor shaft is locked.

• Output phase is open.

• Operating a reciprocating load.

UP1

Main Power
Undervoltage

• Input 3-phase voltage is too low.

• Momentary power failure longer than the time setting of

F628

.

UP2

Control Power
Undervoltage

• This fault is caused by an undervoltage condition at the 5, 15, or the 24 VDC

supply.

• 3-phase input voltage low.

LED Display

LCD Display

Possible Causes