Emergency Off Mode Settings

Program

Protection

Emergency Off Settings

This parameter determines the method used to stop the motor in the event that
an Emergency Off command is received and the system is configured to use
this feature.

This setting may also be associated with the FL terminals to allow the FL relay
to change states when an EOFF condition occurs by setting the FL terminal to
Fault FL (all) (see

F132

).

Note:

A supplemental emergency stopping system should be used with
the ASD. Emergency stopping should not be a task of the ASD
alone.

Settings:

0 — Coast Stop
1 — Deceleration Stop
2 — DC Injection Braking Stop
3 — Deceleration Stop (Decel #4 setting;

F515

)

Direct Access Number — F603

Parameter Type — Selection List

Factory Default — Coast Stop

Changeable During Run — No

Emergency Off DC Injection Application Time

Program

Protection

Emergency Off Settings

When DC Injection is selected at

F603

this parameter determines the time that

the DC Injection braking is applied to the motor.

Direct Access Number — F604

Parameter Type — Numerical

Factory Default — 1.0

Changeable During Run — Yes

Minimum — 0.0

Maximum — 20.0

Units — Seconds

ASD Output Phase Failure Detection

Program

Protection

Phase Loss

This parameter Enables/Disables the monitoring of each phase of the 3-phase
output signal (U, V, or W) of the ASD. If either line is missing, inactive, or not
of the specified level for one second or more, the ASD incurs a trip.

Note:

Autotune checks for phase failures regardless of this setting.

Settings:

0 — Disabled (no detection)
1 — Enabled (Run at Startup and Retry)
2 — Enabled (every Run command and Retry)
3 — Enabled (during Run)
4 — Enabled (at Startup and during Run)
5 — Enabled (detects an ALL-PHASE failure ONLY - will not trip, restarts

at reconnect)

Direct Access Number — F605

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

F603