F523, Pattern group 1 selection – Toshiba H9 User Manual

Page 180

Advertising
background image

172

H9 ASD Installation and Operation Manual

Pattern Group 1 Selection 1

Program

Pattern Run

Speeds

Groups of configured Preset Speeds may be selected and run from this screen.
The execution of grouped Preset Speeds in this manner is called a Pattern
Run
.

One to eight user-selected Preset Speeds may be run sequentially for a user-set
number of repetitions. The group of user-selected Preset Speeds is called a
Pattern Group. The Pattern Run function executes the user-set Pattern
Group
.

Pattern Group 1 is comprised of up to 8 Selections with each Selection being
1 of 15 possible Preset Speed settings. Skip may be selected to ignore a
Selection.

This parameter allows the user to choose one configured Preset Speed that is to
be used as Selection 1 (of 8) for Pattern Group 1. See

F018

for information on

configuring the individual Preset Speeds. Parameters

F524

F530

may be

setup for subsequent Selections 28.

One Preset Speed number (1 – 15) or Skip is selected for Selection 1 (

F523

).

The number of times to repeat Pattern Group 1 is selected at

F522

. Set this

value to 255 to run forever.

Setup Pattern Group 2 at

F531

F539

if more Preset Speed entries are

required.

Pattern Run Setup (for Pattern Group 1)

1.

From Program

⇒ Pattern Run ⇒ Speeds, select the Preset Speeds that are

to be used as the Pattern Group 1 set of Selections. Select a speed from
the 1 – 15 configured presets; 1 speed number per Selection. Set any
unused Selections to Skip.

2.

From Program

⇒ Pattern Run ⇒ Pattern Run ⇒ Pattern Operation

Selection, enable the Pattern Run mode of operation by selecting Seconds
or Minutes as the unit of measure for the Operation Time setting.

3.

From Program

⇒ Pattern Run ⇒ Operation Time, set the run-time for

each Preset Speed selected in step

1

.

4.

Configure two unused discrete input terminals for Pattern Operation
Group 1
and Pattern Operation Trigger Signal.

Note:

Activation of the Pattern Operation Group 1 discrete input
terminal is required to enable Pattern Group 1 for use.
Activation of the Pattern Operation Trigger Signal discrete
input terminal starts the Pattern Group 1 pattern run.

5.

From Program

⇒ Pattern Run ⇒ Pattern Run ⇒ Pattern 1 Repeat, set to

the number of times that Pattern Group 1 is to be run. Set to 255 to run
forever.

6.

From Program

⇒ Pattern Run ⇒ Pattern Run ⇒ Pattern Operation

Mode, set the end-of-pattern command to Reset or Continue.

7.

From the Remote mode (Local|Remote light is off), initiate a Run
command (i.e., F and/or R terminal On).

8.

Connect the Pattern Operation Group 1 input terminal to CC.

9.

Connect the Pattern Operation Trigger Signal input terminal to CC and
the Pattern Run will start and continue as programmed.

10. Open the Pattern Operation Trigger Signal connection to CC to stop the

Pattern Run before its conclusion if required.

Direct Access Number — F523

Parameter Type — Selection List

Factory Default — Skip

Changeable During Run — No

Minimum — Skip

Maximum — 15

Units — Preset Speed Number

Pattern Group 1

Selection

F523 F524 F525 F526 F527 F528 F529 F530

1

2

3

4

5

6

7

8

P

reset

S

p

eed

N

u

m

b

er

Skip Skip Skip Skip Skip Skip Skip Skip

1

1

1

1

1

1

1

1

2

2

2

2

2

2

2

2

3

3

3

3

3

3

3

3

4

4

4

4

4

4

4

4

5

5

5

5

5

5

5

5

6

6

6

6

6

6

6

6

7

7

7

7

7

7

7

7

8

8

8

8

8

8

8

8

9

9

9

9

9

9

9

9

10

10

10

10

10

10

10

10

11

11

11

11

11

11

11

11

12

12

12

12

12

12

12

12

13

13

13

13

13

13

13

13

14

14

14

14

14

14

14

14

15

15

15

15

15

15

15

15

F523

F523