H9 ASD Installation and Operation Manual

V/f Five-Point Setting Frequency 5

Program

Special

V/f Five-Point Setting

The Custom V/f Five-Point Setting Frequency 5 sets the frequency to be
associated with the voltage setting of parameter

F199

(V/f Five-Point Setting

Voltage 5).

See

F190

and

F191

for additional information on this setting.

Direct Access Number — F198

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — No

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

V/f Five-Point Setting Voltage 5

Program

Special

V/f Five-Point Setting

The V/f Five-Point Setting Voltage 5 establishes the output voltage level that
is to be associated with the frequency setting of

F198

(V/f Five-Point Setting

Frequency 5).

The

F701

parameter setting will determine if the selection for this parameter

appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.

The default setting is %.

See

F190

and

F191

for additional information on this setting.

Direct Access Number — F199

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — No

Minimum — 0.0

Maximum — 100.0

Units — V or % (

F701

)

Frequency Priority Selection

Program

Fundamental

Standard Mode Selection

Either Frequency Mode 1 or Frequency Mode 2 may control the output
frequency of the ASD. This parameter determines which of the two will control
the output frequency and the conditions in which control will be switched from
one to the other.

Note:

Frequency Mode is abbreviated as FMOD.

Settings:

0 — FMOD changed by Terminal Board (Frequency Mode)
1 — FMOD (

F208

) (Frequency Mode)

The Frequency Mode 1 or Frequency Mode 2 selection specifies the source of
the input frequency command signal. These selections are performed at

F004

and

F207

, respectively.

If FMOD changed by Terminal Board is selected here, the ASD will follow
the control of the discrete input terminal assigned the function of Frequency
Priority
. The discrete terminal Frequency Priority will toggle control to and
from Frequency Mode 1 and Frequency Mode 2 with each activation/
deactivation.

If FMOD (

F208

) is selected here, the ASD will follow the control of the

Frequency Mode 1 setting for the duration that the commanded frequency of
the Frequency Mode 1 setting is greater than the setting of

F208

.

If the commanded frequency of the Frequency Mode 1 setting is less than or
equal to the setting of

F208

the ASD will follow the setting of Frequency

Mode 2.

Direct Access Number — F200

Parameter Type — Selection List

Factory Default — FMOD (changed by
TB)

Changeable During Run — Yes

F198

F200