Stall Prevention Factor 1

Program

Protection

Stall

This parameter is to be adjusted in the event that the motor stalls when operated
above the base frequency.

If a momentary heavy load occurs the motor may stall before the load current
reaches the stall prevention level setting of

F601

.

A drop in the supply voltage may cause fluctuations of the load current or may
cause motor vibration. A gradual adjustment of this parameter may alleviate
this condition.

Start with a setting of 85 at these parameters and gradually adjust them from
there one at a time until the desired results are produced.

Adjustments to this parameter may increase the load current of the motor and
subsequently warrant an adjustment at the Motor Overload Protection Level
setting.

Direct Access Number — F416

Parameter Type — Numerical

Factory Default — 100

Changeable During Run — No

Minimum — 10

Maximum — 250

Torque Command Selection

Program

Torque

Torque Control

When operating in the Torque Control mode, this parameter allows the user to
select the source of the torque command signal.

Settings:

1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 2-wire
6 — RS485 4-wire
7 — Communication Option Board
8 — RX2 Option (AI1)

Direct Access Number — F420

Parameter Type — Selection List

Factory Default — RX

Changeable During Run — Yes

Tension Torque Bias Input

Program

Torque

Torque Control

This parameter Enables/Disables the Tension Torque Bias input function.

This feature is enabled by selecting a Tension Torque Bias input signal source.

Settings:

0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 2-wire
6 — RS485 4-wire
7 — Communication Option Board
8 — RX2 Option (AI1)

Direct Access Number — F423

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes