Low speed, Reach frequency, F105 – Toshiba H9 User Manual

Page 94: F100, F101, F102

Advertising
background image

86

H9 ASD Installation and Operation Manual

Low-Speed Signal Output Frequency

Program

Terminal

Reach Settings

The Low Speed Signal Output Frequency parameter sets a frequency
threshold that activates the assigned output terminal for the duration that the
ASD output is at or above this setting (see

Table 8 on pg. 241

for the available

output assignments).

Direct Access Number — F100

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

Speed Reach Frequency

Program

Terminal

Reach Settings

The Speed Reach Frequency sets a frequency threshold that, when reached or
is within the bandwidth specified by parameter

F102

, activates the assigned

output terminal for the duration that the ASD output is within the bandwidth
specified (see

Table 8 on pg. 241

for the available output assignments).

Direct Access Number — F101

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

Speed Reach Detection Band

Program

Terminal

Reach Settings

This parameter sets the bandwidth of the Speed Reach Frequency (

F101

)

setting.

Direct Access Number — F102

Parameter Type — Numerical

Factory Default — 2.50

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

Forward/Reverse Run Priority Selection

Program

Terminal

Input Special Functions

The Forward/Reverse Priority Selection determines the operation of the ASD
if the F and R control terminals are activated simultaneously.

Settings:

0 — Reverse
1 — Suspend

The waveforms shown depict the motor response for all combinations of the F
and R terminal settings if the Reverse option is chosen.

The Suspend setting will decelerate the motor to a stop regardless of the
rotation direction when both the F and R control terminals are activated.

Direct Access Number — F105

Parameter Type — Selection List

Factory Default — Suspend

Changeable During Run — No

Simultaneous F and R activation.

Low Speed

Reach
Frequency

F100

F105

Advertising