202

H9 ASD Installation and Operation Manual

Panel Frequency Lockout

Program

Special

Operation Panel Parameters

While operating using the LED Keypad Option this parameter Enables/
Disables
the ability to change the frequency command value.

Settings:

0 — Unlocked
1 — Locked

Direct Access Number — F730

Parameter Type — Selection List

Factory Default — Unlocked

Changeable During Run — Yes

Panel Emergency Off Lockout

Program

Special

Operation Panel Parameters

While operating using the LED Keypad Option this parameter Enables/
Disables
the ability to provide an Emergency Off command.

Settings:

0 — Unlocked
1 — Locked

Direct Access Number — F734

Parameter Type — Selection List

Factory Default — Unlocked

Changeable During Run — No

Panel Reset Lockout

Program

Special

Operation Panel Parameters

While operating using the LED Keypad Option this parameter Enables/
Disables
the ability to initiate a Reset.

Settings:

0 — Unlocked
1 — Locked

Direct Access Number — F735

Parameter Type — Selection List

Factory Default — Unlocked

Changeable During Run — Yes

Command Mode/Frequency Mode Change Lockout

Program

Utilities

Prohibition

This parameter Enables/Disables the ability to change the CMOD/FMOD
settings.

Note:

Command Mode is abbreviated as CMOD.

Note:

Frequency Mode is abbreviated as FMOD.

Settings:

0 — Unlocked
1 — Locked

Direct Access Number — F736

Parameter Type — Selection List

Factory Default — Locked

Changeable During Run — Yes

Lockout All Keys

Program

Utilities

Prohibition

This parameter Enables/Disables EOI keypad operation.

Settings:

0 — Unlocked
1 — Locked

Direct Access Number — F737

Parameter Type — Selection List

Factory Default — Unlocked

Changeable During Run — Yes