F721, F725, F727 – Toshiba H9 User Manual

Page 209: F728, F729

Advertising
background image

H9 ASD Installation and Operation Manual

201

Panel Stop Pattern

Program

Special

Operation Panel Parameters

While operating in the Local mode this parameter determines the method used
to stop the motor when the stop command is issued via the EOI.

The Decel Stop setting enables the Dynamic Braking system that is setup at

F304

or the DC Injection Braking system that is setup at

F250

,

F251

, and

F252

.

The Coast Stop setting allows the motor to stop at the rate allowed by the
inertia of the load.

Settings:

0 — Deceleration Stop
1 — Coast Stop

Note:

The Stop Pattern setting has no effect on the Emergency Off
settings of

F603

. This parameter may also be accessed by

pressing the ESC key from the Frequency Command screen.

Direct Access Number — F721

Parameter Type — Selection List

Factory Default — Deceleration Stop

Changeable During Run — Yes

Panel Torque Command

Program

Special

Operation Panel Parameters

While operating using the LED Keypad Option this parameter sets the torque
command.

Direct Access Number — F725

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.00

Maximum — +250.00

Panel Tension Torque Bias

Program

Special

Operation Panel Parameters

While operating using the LED Keypad Option this parameter sets the Torque
Bias
.

Direct Access Number — F727

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -250.00

Maximum — +250.00

Units — %

Panel Load Sharing Gain

Program

Special

Operation Panel Parameters

While operating using the LED Keypad Option this parameter is used to set
the Load Sharing Gain.

Direct Access Number — F728

Parameter Type — Numerical

Factory Default — 100.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.00

Units — %

Panel Override Multiplication Gain

Program

Special

Operation Panel Parameters

While operating using the LED Keypad Option this parameter provides a
value to be used in the event that

F729

(setting) is selected for the Frequency

Override Multiplying Input (

F661

).

Direct Access Number — F729

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — -100.00

Maximum — 100.00

Units — %

F721

F729