108

H9 ASD Installation and Operation Manual

V/I Input Point 2 Rate

Program

Torque

Setpoints

This parameter is used to set the gain and bias of the V/I input terminal when
the V/I terminal is used as the control input while operating in the Torque
Control
mode.

Torque Control is accomplished by establishing an associated V/f output pattern
for a given V/I input level.

This parameter sets V/I Input Point 2 Rate and is the output torque value that
is associated with the setting of V/I Input Point 2 Setting when operating in
the Torque Control mode.

This value is entered as 0% to 250% of the rated torque.

See V/I Input Point 1 Rate for more information on this setting.

Direct Access Number — F206

Parameter Type — Numerical

Factory Default — 100.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.00

Units — %

Frequency Mode 2

Program

Fundamental

Standard Mode Selection

This parameter is used to set the source of the frequency command signal to be
used as Frequency Mode 2 in the event that Frequency Mode 1 is disabled or
if Frequency Mode 2 is set up as the primary control parameter. See

F004

and

F200

for additional information on this setting.

Settings:

1 — V/I
2 — RR
3 — RX
4 — Not Used
5 — EOI Keypad
6 — RS485
7 — Communication Option Board
8 — RX2 Option (AI1)
9 — Option V/I
10 — UP/DOWN Frequency (terminal board)
11 — Pulse Input (option)
12 — Pulse Input (motor CPU)
13 — Binary/BCD Input (option)

Direct Access Number — F207

Parameter Type — Selection List

Factory Default — V/I

Changeable During Run — Yes

Frequency Mode Priority Switching Frequency

Program

Fundamental

Standard Mode Selection

This parameter establishes a threshold frequency that will be used as a reference
when determining when to switch the output frequency control source from the
Frequency Mode 1 setting to the Frequency Mode 2 setting.

See

F200

for additional information on this setting.

Direct Access Number — F208

Parameter Type — Numerical

Factory Default — 0.10

Changeable During Run — Yes

Minimum — 0.10

Maximum — Max. Freq. (

F011

)

Units — Hz

F206

F208