H9 ASD Installation and Operation Manual

147

Commercial Power/ASD Switching Frequency

Program

Terminal

Line Power Switching

When enabled at

F354

and with a properly configured discrete output terminal,

this parameter sets the frequency at which the At Frequency Powerline
Switching
function engages.

The At Frequency Powerline Switching function commands the system to
discontinue using the output of the drive and to switch to commercial power
once reaching the frequency set here.

See parameter

F354

for more information on this setting.

Direct Access Number — F355

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

ASD-side Switching Wait Time

Program

Terminal

Line Power Switching

This parameter determines the amount of time that the drive will wait before
outputting a signal to the motor once the switch-to-drive-output criteria has
been met.

See parameter

F354

for more information on this setting.

Direct Access Number — F356

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.10

Maximum — 10.00

Units — Seconds

Commercial Power Switching Wait Time

Program

Terminal

Line Power Switching

This parameter determines the amount of time that the drive will wait before
allowing commercial power to be applied to the motor once the switch-to-
commercial-power criteria has been met.

See parameter

F354

for more information on this setting.

Direct Access Number — F357

Parameter Type — Numerical

Factory Default — 0.62

Changeable During Run — Yes

Minimum — (ASD-dependent)

Maximum — 10.00

Units — Seconds

Commercial Power Switching Freq. Hold Time

Program

Terminal

Line Power Switching

This parameter determines the amount of time that the connection to
commercial power is maintained once the switch-to-drive-output criteria has
been met.

See parameter

F354

for more information on this setting.

Direct Access Number — F358

Parameter Type — Numerical

Factory Default — 2.00

Changeable During Run — Yes

Minimum — 0.10

Maximum — 10.00

Units — Seconds

PID Control Switching

Program

Feedback

Feedback Settings

This parameter is used to set the PID control mode.

Selecting Process PID uses the upper and lower limit settings of parameters

F367

and

F368

.

Selecting Speed PID uses the upper and lower limit settings of parameters

F370

and

F371

.

Settings:

0 — PID Off
1 — Process PID
2 — Speed PID
3 — Easy Positioning PID (unavailable at the time of this release)

Direct Access Number — F359

Parameter Type — Selection List

Factory Default — PID Off

Changeable During Run — No