Connecting the h9 asd, Power connections, Figure 2 on pg. 16 – Toshiba H9 User Manual

Page 24: Danger

Advertising
background image

16

H9 ASD Installation and Operation Manual

Connecting the H9 ASD

Refer to the section titled

Installation Precautions on pg. 4

and the section titled

Lead Length

Specifications on pg. 20

before attempting to connect the H9 ASD and the motor to electrical power.

Power Connections

Contact with the 3-phase input or output terminals may cause an electrical shock

resulting in injury or loss of life.

See

Figure 20 on pg. 26

for a system I/O connectivity schematic.

An inductor (DCL) may be connected across the PO and PA/+ terminals to provide additional filtering.
When not used, a jumper must be connected across these terminals (see

Figure 20 on pg. 26

).

PA/+ and PB are used for the DBR connection if using a braking resistor.

PC/- is the negative terminal of the DC bus.

R/L1, S/L2, and T/L3 are the 3-phase input supply terminals for the H9 ASD.

U/T1, V/T2, and W/T3 are the output terminals of the H9 ASD that connect to the motor.

The location of the Charge LED for the smaller typeform ASD is provided in

Figure 2

. The Charge

LED is located on the front door of the enclosure of the larger ASDs.

Figure 2. Typical H9 ASD input/output terminals and the

Grounding Capacitor Switch

.

DANGER

DANGER

Charge LED

Grounding Capacitor Switch — Pull for Small capacitance/Push for Large capacitance.

Advertising