Preset Speed 1 Operation Mode

Program

Pattern Run

Operation Mode

This parameter is enabled at

F560

and is used to set the speed, torque, and

direction of Preset Speed 1.

This screen is comprised of 4 fields that are labeled as follows: Direction, Acc/
Dec Group
, V/f Group, and Torque Limit Group. Scroll to the field of
interest and press the scroll knob (Enter). Using the scroll knob, set the value
and press the scroll knob (Enter).

Parameters

F562

F575

are used to set the functions listed here for Preset

Speeds 215.

When using communications write the appropriate word to location

F561

as

indicated below.

Settings:

0 — Forward Run
1 — Reverse Run
2 — Accel/Decel Switching 1
4 — Accel/Decel Switching 2
8 — V/f Switching Signal 1
16 — V/f Switching Signal 2
32 — Torque Limit Switching Signal 1
64 — Torque Limit Switching Signal 2

Direct Access Number — F561

Parameter Type — Selection List

Factory Default — Forward Run

Changeable During Run — No

Preset Speed 2 Operation Mode

Program

Pattern Run

Operation Mode

Same as Preset Speed 1 Operation Mode (see

F561

).

Direct Access Number — F562

Parameter Type — Selection List

Factory Default — Forward Run

Changeable During Run — No

Preset Speed 3 Operation Mode

Program

Pattern Run

Operation Mode

Same as Preset Speed 1 Operation Mode (see

F561

).

Direct Access Number — F563

Parameter Type — Selection List

Factory Default — Forward Run

Changeable During Run — No

F/R

V/f Switch

Torque Limit

Switch 2

A/D Switch

1

2

4

8

16

32

64

0

1

1

0

1

1

0

Writing the following data to location

F561

via communications results in:

Forward Run, A/D SW 2, V/f SW 3, Torque Lim SW 4.

{

{

{

{

0=F
1=R

00=A/D 1
01=A/D 2

10=A/D 3
11=A/D 4

00=V/f 1
01=V/f 2
10=V/f 3
11=V/f 4

00=T-Lim 1
01=T-Lim 2

10=T-Lim 3
11=T-Lim 4