112

H9 ASD Installation and Operation Manual

RR Input Point 1 Rate

Program

Torque

Setpoints

This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Torque
Control
mode.

RR Input Torque Control Setup

Perform the following setup to allow the system to receive Torque Control
input at the RR input terminal:

• Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Frequency Mode

RR.

• Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode

Selection

Terminal Block.

Torque Control

Perform the following setup to allow the system to perform Torque Control
from the RR input terminal:

• Set RR Input Point 1 Rate (

F214

).

• Set RR Input Point 1 Setting (

F210

) — the input analog signal level that

corresponds to the torque setting at RR Input Point 1 Rate.

• Set RR Input Point 2 Rate (

F215

).

• Set RR Input Point 2 Setting (

F212

) — the input analog signal level that

corresponds to the frequency setting at RR Input Point 2 Rate.

• Provide a Run command (F and/or R).

Torque Control is accomplished by establishing an associated V/f output pattern
for a given RR input level.

Once set, as the RR input voltage changes, the output torque of the ASD will
vary in accordance with the above settings.

This parameter sets RR Input Point 1 Rate and is the output torque value that
is associated with the setting of RR Input Point 1 Setting when operating in
the Torque Control mode.

This value is entered as 0% to 250% of the rated torque.

Direct Access Number — F214

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.00

Units — %

Torque Settings

RR Input Point 2 Rate

Program

Torque

Setpoints

This parameter is used to set the gain and bias of the RR input terminal when
the RR terminal is used as the control input while operating in the Torque
Control
mode.

Torque Control is accomplished by establishing an associated V/f output
pattern for a given RR input level.

This parameter sets RR Input Point 2 Rate and is the output torque value that
is associated with the setting of RR Input Point 2 Setting when operating in
the Torque Control mode.

This value is entered as 0% to 250% of the rated torque.

See RR Input Point 1 Rate for more information on this setting.

Direct Access Number — F215

Parameter Type — Numerical

Factory Default — 100.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.00

Units — %

F214

F215