88

H9 ASD Installation and Operation Manual

Option V/I Terminal Voltage/Current Selection

Program

Frequency

V/I Settings

This parameter is used to set the AI2 input terminal to receive either current or
voltage as a control signal.

Note:

The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.

See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
more information on the function of this terminal.

Settings:

0 — Voltage Input
1 — Current Input

Direct Access Number — F109

Parameter Type — Selection List

Factory Default — Voltage Input

Changeable During Run — No

Always ON 1 Terminal 1

Program

Terminal

Input Terminals

ON

This parameter is used to set the functionality of the virtual discrete input
terminal ON. As a virtual terminal, the ON control terminal exists only in
memory and is considered to always be in its True (connected to CC) state.

It is often practical to assign a function to this terminal that the user desires to
be maintained regardless of external conditions or operations.

This parameter sets the programmable ON terminal to any one of the user-
selectable functions listed in

Table 5 on pg. 236

.

Direct Access Number — F110

Parameter Type — Selection List

Factory Default — Unassigned

Changeable During Run — No

Input Terminal 1 (F) Function

Program

Terminal

Input Terminals

This parameter is used to set the functionality of the F discrete input terminal.

In addition, this input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable F terminal to any one of the user-
selectable functions listed in

Table 5 on pg. 236

.

Direct Access Number — F111

Parameter Type — Selection List

Factory Default—Forward

Forward

Changeable During Run — No

Input Terminal 2 (R) Function

Program

Terminal

Input Terminals

This parameter is used to set the functionality of the R discrete input terminal.

In addition, this input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable R terminal to any one of the user-
selectable functions listed in

Table 5 on pg. 236

.

Direct Access Number — F112

Parameter Type — Selection List

Factory Default — Reverse

Reverse

Changeable During Run — No

Input Terminal 3 (ST) Function

Program

Terminal

Input Terminals

This parameter is used to set the functionality of the ST discrete input terminal.

In addition, this input terminal must be specified as Normally Open or
Normally Closed.

This parameter sets the programmable ST terminal to any one of the user-
selectable functions listed in

Table 5 on pg. 236

.

Direct Access Number — F113

Parameter Type — Selection List

Factory Default — Standby

Standby

Changeable During Run — No

F109

F113