F261, F262 – Toshiba H9 User Manual

Page 135

Advertising
background image

H9 ASD Installation and Operation Manual

127

Jog Stop Pattern

Program

Frequency

Jog Settings

This parameter sets the stopping method used while operating in the Jog mode.

Note:

This parameter setting is used for the Jog operation only. The
Emergency Off stopping method setting of parameter

F603

has

priority over this setting and changes made here do not affect the
function or setting of parameter

F603

.

Settings:

0 — Deceleration Stop
1 — Coast Stop
2 — DC Injection Braking Stop

Direct Access Number — F261

Parameter Type — Selection List

Factory Default — Deceleration Stop

Changeable During Run — Yes

Panel Operation Jog Mode

Program

Frequency

Jog Settings

This parameter enables the Jog command to be received from the EOI. When
disabled the Jog command received from the EOI is ignored.

Jog commands may also be received from the Terminal Board. Priority as to
which is allowed to override the other is selected at

F106

.

The priority selection at

F106

enables the selected source for Jog control and

disables the other. The

F106

setting overrides this parameter setting.

Settings:

0 — Disabled
1 — Enabled

Direct Access Number — F262

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — Yes

F261

F262