H9 ASD Installation and Operation Manual

233

My Function Selection

Program

My Function

This parameter Enables/Disables the configured My Function feature of the
H9 ASD.

Settings:

0 — None (Disabled)
1 — My Function with Terminal Board Signal (discrete terminal activation)
2 — My Function Always On

My Function

The My Function feature is configured using the settings of

F900

to

F977

and

is used to enhance the programmability of the H9 ASD by performing two
programmable functions: 1) the Combined Terminal Function, and 2) Logic
Operations.

Combined Terminal Function

Assigning more than one function to a discrete input terminal provides two
advantages: it effectively expands the number of input terminals, and reduces
the number of cables required to support the input/output functions (e.g.,
assigning ST and F to one terminal). Using Virtual Terminals 14 (

F973

F976

) are required to use this function.

In the example below, the ST terminal assignment and the F terminal
assignment will be combined as one terminal to illustrate this feature. However,
any two of the discrete input terminal assignments listed in

Table 5 on pg. 236

may be combined in this manner.

Setup (example)

1.

Disable the My Function parameter at

F977

to prevent the system from

starting upon completion of the setup.

2.

Assign the ST function to the S1 terminal (

F115

).

3.

Assign the F function to Virtual Input Terminal 1 (

F973

).

4.

Set Input Function Target 1 to 5 (

F900

). This setting assigns S1 as the

control input terminal.

5.

Set Output Function Assigned to 21 (

F905

). This setting is a command

that writes the

F115

selection (S1) to Virtual Input Terminal 1, activating

both.

6.

Enable the My Function parameter at

F977

by selecting My Function

Always On or selecting My Function With TB Signal.

If set to My Function Always On, the combination of ST and F are
always On (both are connected to CC only during the S1 activation).

If set to My Function With TB Signal, set a discrete input terminal to My
Function Run Signal
and connect it to CC to enable My Function.
Connect S1 to CC to activate the ST+F function. A disconnection at either
terminal will terminate the My Function programming (discrete input
terminal My Function Run Signal is Anded with discrete input terminal
S1).

Connect S1 to CC and the F-to-CC

+

the ST-to-CC functions will be carried

out using only S1.

With the aforementioned setup completed, provide a Frequency Command
(

F004

) and the motor will run at the commanded frequency.

(Continued on

pg. 234

)

Direct Access Number — F977

Parameter Type — Selection List

Factory Default — None (Disabled)

Changeable During Run — No

This parameter must always be set to
None at the start of the My Function
setup and remain set to None until all
of the My Function parameter
settings have been confirmed as
being correct.

If enabled for normal operation using
settings 1 or 2, the motor may start
and engage the driven equipment
unexpectedly upon receiving a Run
signal during the My Function setup.

DANGER

F977

F977