F813, F814, F820 – Toshiba H9 User Manual

Page 216: F825

Advertising
background image

208

H9 ASD Installation and Operation Manual

Point 2 Setting

Program

Communications

Communication Reference Adjust

This parameter is used to set the gain and bias of the Communications
Reference
speed control input.

See

F811

for more information on this setting.

This parameter sets the Communications Reference input value that represents
Communications Reference Speed Setpoint #2 (frequency). This value is
entered as 0 to 100% of the Communications Reference input value range.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Direct Access Number — F813

Parameter Type — Numerical

Factory Default — 100

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Units — %

Point 2 Frequency

Program

Communications

Communication Reference Adjust

This parameter is used to set the gain and bias of the Communications
Reference
speed control input.

See

F811

for more information on this setting.

This parameter sets the Communications Reference Speed Setpoint #2.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Direct Access Number — F814

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

Baud Rate (RS485 4-wire)

Program

Communications

Communication Settings

This parameter sets the RSRS485 baud rate.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Settings:

0 — 9600 bps
1 — 19200 bps
2 — 38400 bps

Direct Access Number — F820

Parameter Type — Selection List

Factory Default — 19200

Changeable During Run — Yes

RS485 Send Wait Time (RS485 4-wire)

Program

Communications

Communication Settings

This parameter sets the RS485 response delay time.

Changes made to this parameter require that the power be cycled (Off then On)
for the changes to take effect.

Direct Access Number — F825

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 2.00

Units — Seconds

F813

F825