H9 ASD Installation and Operation Manual

179

Speed 13 Operation Time

Program

Pattern Run

Operation Time

This parameter sets the run-time for Preset Speed #13.

This time is effective when used with Group Speeds and non-Group Speeds.

If the Auto-Restart function is activated, the search time required for the Auto-
Restart
function will be subtracted from the Operation Time setting; resulting
in a shorter run time.

Direct Access Number — F552

Parameter Type — Numerical

Factory Default — 5.0

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000.0

Units —

F520

Setting

Speed 14 Operation Time

Program

Pattern Run

Operation Time

This parameter sets the run-time for Preset Speed #14.

This time is effective when used with Group Speeds and non-Group Speeds.

If the Auto-Restart function is activated, the search time required for the Auto-
Restart
function will be subtracted from the Operation Time setting; resulting
in a shorter run time.

Direct Access Number — F553

Parameter Type — Numerical

Factory Default — 5.0

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000.0

Units —

F520

Setting

Speed 15 Operation Time

Program

Pattern Run

Operation Time

This parameter sets the run-time for Preset Speed #15.

This time is effective when used with Group Speeds and non-Group Speeds.

If the Auto-Restart function is activated, the search time required for the Auto-
Restart
function will be subtracted from the Operation Time setting; resulting
in a shorter run time.

Direct Access Number — F554

Parameter Type — Numerical

Factory Default — 5.0

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000.0

Units —

F520

Setting

Preset Speed Operation Mode

Program

Pattern Run

Operation Mode

This parameter is used to set the Preset Speed operating mode.

Select Disabled at this parameter to use the speed command only for Preset
Speed
operation.

Select Enabled at this parameter to apply the control settings of

F561

F575

to

the associated Preset Speed while operating in the Preset Speed mode.

Settings:

0 — Disabled (Preset Speed Only)
1 — Enabled (Full Preset Speed Mode)

Direct Access Number — F560

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

F552