H9 ASD Installation and Operation Manual

169

Deceleration Time 3

Program

Special

Accel/Decel #1 – #4 Settings

This parameter specifies the time in seconds for the output of the ASD to go
from the Maximum Frequency to 0.0 Hz for the #3 Deceleration profile.

The Accel/Decel pattern may be set using

F502

. The minimum Accel/Decel

time may be set using

F508

.

Note:

A deceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel
, Stall, and Ridethrough settings may lengthen the
deceleration times.

Direct Access Number — F511

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

Acceleration/Deceleration Pattern 3

Program

Special

Accel/Decel #1 – #4 Settings

This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the #3 Accel/Decel
parameter.

Settings:

0 — Linear
1 — S-Pattern 1
2 — S-Pattern 2

Direct Access Number — F512

Parameter Type — Selection List

Factory Default — Linear

Changeable During Run — Yes

Acceleration/Deceleration Switching Frequency 2

Program

Special

Accel/Decel Special

This parameter sets the frequency at which the acceleration control is switched
from the Accel #2 profile to the Accel #3 profile during a multiple-acceleration
profile configuration.

Direct Access Number — F513

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

Acceleration Time 4

Program

Special

Accel/Decel #1 – #4 Settings

This parameter specifies the time in seconds for the output of the ASD to go
from 0.0 Hz to the Maximum Frequency for the #4 Acceleration profile. The
Accel/Decel pattern may be set using

F502

. The minimum Accel/Decel time

may be set using

F508

.

Note:

An acceleration time shorter than the load will allow may cause
nuisance tripping and mechanical stress to loads. Automatic
Accel/Decel
, Stall, and Ridethrough settings may lengthen the
acceleration times.

Direct Access Number — F514

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.1

Maximum — 6000

Units — Seconds

F511

F514