H9 ASD Installation and Operation Manual

PTC2 Thermal Selection

Program

Special

Special Parameters

PTC2 Thermal Selection

This parameter Enables/Disables the optional external thermal detection circuit
of the Expansion IO Card Option 2. A thermistor is connected from TH1+ to
TH1- of TB4 on the Expansion IO Card Option 2.

Should the thermistor resistance reading fall below 50

Ω because of an over-

temperature condition or exceed 3000

Ω because of an open circuit an External

Thermal Fault (OH2) will be incurred.

Note:

While this parameter is Enabled, the system cannot be restarted
until the thermistor value recovers to the level of 1.8k

Ω from an

over-temperature condition. An Auto-restart will not be initiated
subsequent to an External Thermal Trip (OH2). A manual
restart will be required in the event of an OH2 trip.

Settings:

0 — Disabled
1 — Detect Disconnect

Direct Access Number — F638

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

Braking Resistance Overload Time (10x rated torque)

Program

Protection

Dynamic Braking

This parameter sets the time that the braking resistor is allowed to sustain and
overload condition before a trip is incurred.

This feature is useful for applications that have a fluctuating load or for loads
that require a long deceleration time.

Direct Access Number — F639

Parameter Type — Numerical

Factory Default — 5.0

Changeable During Run — No

Minimum — 0.1

Maximum — 600.0

Units — Seconds

Step-Out Current Detection Level

Program

Motor

PM Motor

This parameter is used with synchronous motor applications only.

Contact Toshiba Customer Service Department for information on this
parameter.

Direct Access Number — F640

Parameter Type — Numerical

Factory Default — 100

Changeable During Run — Yes

Minimum — 10

Maximum — 150

Units — %

Step-Out Current Detection Time

Program

Motor

PM Motor

This parameter is used with synchronous motor applications only.

Contact Toshiba Customer Service Department for information on this
parameter.

Direct Access Number — F641

Parameter Type — Numerical

Factory Default — 00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 25.0

Units — Seconds

F638

F641