Direct Access Parameter Information

The H9 ASD has the ability to allow the user direct access to the motor control functions. There are two
ways in which the motor-control parameters may be accessed for modification: Program

applicable

menu path or Program

⇒ Direct Access ⇒ applicable parameter number. Both methods access the

parameter via the Program mode. Once accessed, the parameter may be viewed or changed.

The Program mode allows the user to develop an application-specific motor-control profile. Motor
control functions may be set to accommodate specific power and timing requirements for a given
application. The configurable parameters of the Program mode that have user-accessible Parameter
Numbers
are listed and described below.

Note: Parameter selections are preceded by the number used to select an item if using communications to

write to a parameter location in memory (i.e., F000

0-Manual, 1- No Trip on Acc/Dec, 2-No trip on

Acc Only, etc.).

Note: The setup procedures included within this section may require a Reset before performing the procedure.

Application-specific settings may then be performed. The pre-Reset conditions may be saved (see

F007

).

Note: Communications setting changes will require that the power be removed and then re-applied for the

changes to take affect.

Direct Access Parameters/Numbers

Automatic Acceleration/Deceleration

Program

Fundamental

Accel/Decel #1 Settings

This parameter is used to allow the ASD to adjust the acceleration and
deceleration rates in accordance with the applied load automatically.

The adjusted acceleration and deceleration times range from 12.5% to 800% of
the programmed values for Acceleration Time #1 (

F009

) and Deceleration

Time #1 (

F010

).

Settings:

0 — Manual
1 — Automatic ACC/DEC
2 — Automatic ACC Only

Note:

The motor and the load must be connected prior to selecting
Automatic Acceleration/Deceleration.

Direct Access Number — F000

Parameter Type — Selection List

Factory Default — Manual

Changeable During Run — No

Automatic Torque Boost

Program

Fundamental

Motor Set #1

This parameter allows the ASD to adjust the output torque in accordance with
the applied load automatically. When enabled Autotuning is performed — the
motor should be connected before performing an Autotune.

Settings:

0 — Disabled
1 — Automatic Torque Boost + Autotuning
2 — Sensorless Vector Control + Autotuning

Direct Access Number — F001

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

F000

F001