Cable/Terminal/Torque Specifications

Installation should conform to the 2005 National Electrical Code Article 110 (NEC

) (Requirements for Electrical

Installations), all regulations of the Occupational Safety and Health Administration, and any other
applicable national, regional, or industry codes and standards.

Note:

The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the H9 ASD. Application-specific applicables, wire insulation
type, conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the H9 ASD.

Note:

Cable/Terminal specifications are based on the rated current of the H9 ASD and Do
Not
include the 10% Service Factor.

Note:

Use only 75° C copper wire/cable for motor and power connections.

For further installation information see the section titled

Installation and Connections on pg. 14

.

Note:

(*) Indicates that the item is one of a set of two parallel cables.

Table 20. 230-Volt H9 ASD Cable/Terminal/Torque Specifications.

Model

Number

VT130H9U

MCP Rating

(Amps)

Wire/Cable Size

Lug Size Range

Terminal

Board

Torque

AWG or kcmil

Input/Output Power

Wire-Size/Lug-Capacity for

Input/Output Power

TB1 – 4

Terminals

3Ø-Input 3Ø-Output

Recommended Maximum

3Ø-Input

3Ø-Output

In-Lbs./Nm

2035

30

14

10

14 to 8

20

(3-core shield)

5.3/0.6

11.5/1.3

2055

30

10

10

2080

50

8

8

12 to 8

17.7/2.0

2110

50

8

8

2160

75

6

3

8 to 3

21/2.4

2220

100

4

3

2270

125

3

3

2330

150

2

2

12 to 1/0

4 to 1/0

50/5.7

53/6

2400

175

1/0

4/0

6 to 250

2 to 300

275/31

168/19

2500

200

2/0

4/0

2600

250

3/0

4/0

2750

300

4/0

4/0

210K

400

*3/0

*1/0

6 to 250

275/31

212K

500

*250

*250