H9 ASD Installation and Operation Manual

Lead Length Specifications

Adhere to the NEC and any local codes during the installation of ASD/Motor systems. Excessive lead
lengths may adversely effect the performance of the motor. Special cables are not required. Lead lengths
from the ASD to the motor in excess of those listed in

Table 1

may require filters to be added to the output

of the ASD.

Table 1

lists the suggested maximum lead lengths for the listed motor voltages.

Note:

Contact Toshiba for application assistance when using lead lengths in excess of those
listed.

Exceeding the peak voltage rating or the allowable thermal rise time of the motor
insulation will reduce the life expectancy of the motor.

When operating in the Vector Control mode the carrier frequency should be set to
2.2 kHz or above.

Table 1.

Model

PWM Carrier

Frequency

NEMA MG-1-1998 Section IV Part 31

Compliant Motors

2

230 Volt

All

1000 feet

460 Volt

< 5 kHz

600 feet

≥ 5 kHz

300 feet