131

Jump Frequency 1 Bandwidth

Program

Special

Jump Frequencies

This parameter establishes a plus-or-minus value for Jump Frequency #1 (see

F270

).

Direct Access Number — F271

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 30.00

Units — Hz

Jump Frequency 2

Program

Special

Jump Frequencies

Same as Jump Frequency #1 (

F270

) and is used when multiple frequencies are

to be jumped (see the plus-or-minus value setting at

F273

). When multiple

jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.

Direct Access Number — F272

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

Jump Frequency 2 Bandwidth

Program

Special

Jump Frequencies

This parameter establishes a plus-or-minus value for Jump Frequency #2
(

F272

).

Direct Access Number — F273

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 30.0

Units — Hz

Jump Frequency 3

Program

Special

Jump Frequencies

Same as Jump Frequency #1 (

F270

) and is used when multiple frequencies are

to be jumped (see the plus-or-minus value setting at

F275

).

When multiple jump frequencies overlap, the system will recognize the lowest
and the highest frequencies as one jump range.

Direct Access Number — F274

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

Jump Frequency 3 Bandwidth

Program

Special

Jump Frequencies

This parameter establishes a plus-or-minus value for Jump Frequency #3
(

F274

).

Direct Access Number — F275

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 30.0

Units — Hz

Preset Speed 8

Program

Frequency

Preset Speeds

This parameter assigns an output frequency to binary number 1000 and is
identified as Preset Speed #8. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see

F018

for more information on

this parameter).

Direct Access Number — F287

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — Lower Limit (

F013

)

Maximum — Upper Limit (

F012

)

Units — Hz