UP/DOWN Frequency (up) Frequency Step

No Path — Direct Access Only

This parameter sets the frequency increase amount for each activation of the
UP/DOWN Frequency (up) terminal activation. The rate of the frequency
increase is set at Acceleration Time 1 (

F009

).

See

F264

for more information on this parameter.

Direct Access Number — F265

Parameter Type — Numerical

Factory Default — 0.10

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

UP/DOWN Frequency (down) Response Time

No Path — Direct Access Only

This parameter sets the system-response delay to the initial activation of the
discrete input terminal UP/DOWN Frequency (down). Also sets the activation
delay of subsequent terminal activations of the UP/DOWN Frequency (down)
terminal during an activate-and-hold.

See

F264

for more information on this parameter.

Direct Access Number — F266

Parameter Type — Numerical

Factory Default — 0.1

Changeable During Run — Yes

Minimum — 0.0

Maximum — 10.0

Units — Seconds

UP/DOWN Frequency (down) Frequency Step

No Path — Direct Access Only

F267

—Sets the frequency decrease amount for each activation of the UP/

DOWN Frequency (down) terminal activation. The rate of the frequency
decrease is set at Deceleration Time 1 (

F010

).

See

F264

for more information on this parameter.

Direct Access Number — F267

Parameter Type — Numerical

Factory Default — 0.10

Changeable During Run — Yes

Minimum — 0.00

Maximum — Max. Freq. (

F011

)

Units — Hz

Initial UP/DOWN Frequency

No Path — Direct Access Only

At power up or after a reset, this parameter setting is used to provide a starting
frequency for the UP/DOWN Frequency function.

See

F269

for more information on this parameter setting.

Direct Access Number — F268

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — Lower Limit (

F013

)

Maximum — Upper Limit (

F012

)

Units — Hz

Initial UP/DOWN Frequency Rewriting

No Path — Direct Access Only

At power down, and when enabled, this parameter writes the running frequency
into the

F268

location and, upon a system restart, uses this setting as the startup

frequency.

Disable this parameter and set parameter

F268

to the desired startup frequency

if the same starting frequency is required at each startup.

Note:

This parameter setting may be different at each startup when
enabled.

Settings:

0 — Disabled
1 — Enabled (Overwrite

F268

at Power Off or Reset)

Direct Access Number — F269

Parameter Type — Selection List

Factory Default — Enabled

Changeable During Run — Yes

F265