H9 ASD Installation and Operation Manual

Regenerative Braking Torque Limit 1

Program

Torque

Torque Limit Settings

This parameter determines the source of the Regenerative Torque Limit
control signal.

If Setting is selected, the value set at

F443

is used for this parameter.

Settings:

1 — V/I
2 — RR
3 — RX
4 —

F443

(setting)

Direct Access Number — F442

Parameter Type — Selection List

Factory Default —

F443

Setting

Changeable During Run — Yes

Regenerative Braking Torque Limit 1 Level

Program

Torque

Torque Limit Settings

This parameter provides a value to be used as the Regeneration Torque Limit
#1
if

F443

is selected at parameter

F442

.

Set this parameter to 250% to disable this function.

Direct Access Number — F443

Parameter Type — Numerical

Factory Default — 250.0 (Disabled)

Changeable During Run — Yes

Minimum — 0.00

Maximum — 249.9

Units — %

Power Running Torque Limit 2 Level

Program

Torque

Manual Torque Limit Settings

This parameter is used to set the positive torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.

Direct Access Number — F444

Parameter Type — Numerical

Factory Default — 250.0 (Disabled)

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.0 (Disabled)

Units — %

Regenerative Braking Torque Limit 2 Level

Program

Torque

Manual Torque Limit Settings

This parameter is used to set the negative torque upper limit for the #2 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.

Direct Access Number — F445

Parameter Type — Numerical

Factory Default — 250.0 (Disabled)

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.0 (Disabled)

Units — %

Power Running Torque Limit 3 Level

Program

Torque

Manual Torque Limit Settings

This parameter is used to set the positive torque upper limit for the #3 motor
profile when multiple motors are controlled by a single drive or when a single
motor is to be controlled by multiple profiles.

Direct Access Number — F446

Parameter Type — Numerical

Factory Default — 250.0 (Disabled)

Changeable During Run — Yes

Minimum — 0.00

Maximum — 250.0 (Disabled)

Units — %

F442

F446