248

H9 ASD Installation and Operation Manual

OC

Over Current

ASD output current greater than

F601

setting.

• Defective IGBT (U, V, or W).

• ASD output to the motor is connected incorrectly.

Disconnect the motor and retry.

• ASD output phase-to-phase short.

• The ASD is starting into a spinning motor.

• Motor/machine jammed.

• Mechanical brake engaged while the ASD is starting or

while running.

• Accel/Decel time is too short.

• Voltage Boost setting is too high.

• Load fluctuations.

• ASD operating at an elevated temperature.

*OH

Overheat

ASD ambient temperature
excessive.

• ASD is operating at an elevated temperature.

• ASD is too close to heat-generating equipment.

• Cooling fan vent is obstructed (see

Mounting the H9

ASD on pg. 15

).

• Cooling fan is inoperative.

• Internal thermistor is disconnected.

OJ

Timer

Run-time counter exceeded.

Type Reset required; select Clear run timer.

*OLI

ASD Overload

Load requirement in excess of
the capability of the ASD.

• The carrier frequency is too high.

• An excessive load.

• Acceleration time is too short.

• DC damping rate is set too high.

• The motor is starting into a spinning load after a

momentary power failure.

• The ASD is improperly matched to the application.

OLM

Motor Overload

Load requirement in excess of
the capability of the motor.

• V/f parameter improperly set.

• Motor is locked.

• Continuous operation at low speed.

• The load is in excess of what the motor can deliver.

*OLR

Resistor
Overload

Excessive current at the
Dynamic Braking Resistor.

• Deceleration time is too short.

• DBR configuration improperly set.

LED

Display

LCD

Display

Description

Possible Causes