F005 on pg. 78, F005, F006 – Toshiba H9 User Manual

Page 86

Advertising
background image

78

H9 ASD Installation and Operation Manual

FM Output Terminal Function

Program

Terminal

Analog Output Terminals

This parameter is used to set the output function of the FM analog output
terminal. The FM output terminal produces an output current or voltage that is
proportional to the magnitude of the function assigned to this terminal (select
current or voltage at

F681

). The available assignments for this output terminal

are listed in

Table 6 on pg. 239

.

Note: To read voltage at this terminal connect a 100 – 500

Ω

resistor from

the FM (+) terminal to the CC (-) terminal. Using a voltmeter read
the voltage across the 100 – 500

Ω

resistor.

To read current at this terminal connect a 100 – 500

Ω

resistor from

the FM (+) terminal through a series Ammeter to the CC (-) terminal.

The FM analog output has a maximum resolution of 1/1024 and a
maximum load rating of 500 ohms.

FM Terminal Setup Parameters

F005

— Set FM Function

F006

— Calibrate FM Terminal

F681

— Voltage/Current Output Switching Selection

F682

— Output Response Polarity Selection

F683

— Set Zero Level

Direct Access Number — F005

Parameter Type — Selection List

Factory Default — DC (Bus) Voltage

Changeable During Run — Yes

FM Output Terminal Adjustment

Program

Terminal

Analog Output Terminals

This parameter is used to calibrate the FM analog output.

To calibrate the FM analog output, connect a meter (current or voltage) as
described at

F005

.

With the drive running at a known value (e.g., output frequency), adjust this
parameter until the assigned function produces the desired DC level output at
the FM output terminal.

See

F005

for more information on this setting.

Direct Access Number — F006

Parameter Type — Numerical

Factory Default — 493

Changeable During Run — Yes

Minimum — 1

Maximum — 1280

FM

F005

F006