F453, F458, F460 – Toshiba H9 User Manual

Page 168: F461, F462, F463

Advertising
background image

160

H9 ASD Installation and Operation Manual

Stall Prevention During Regeneration

Program

Protection

Stall

This function of this parameter is to disable the Overvoltage Stall (

F305

) and

the Overcurrent Stall (

F017

) function during regeneration only.

Application-specific conditions may occur that warrant disabling the Stall
function during regeneration.

Settings:

0 — Disabled (Stall During Regenerative Braking)
1 — Enabled (No Stall During Regenerative Braking)

Direct Access Number — F453

Parameter Type — Selection List

Factory Default — Enabled

Changeable During Run — Yes

Current Control Proportional Gain

Program

Feedback

PG Settings

This parameter sets the sensitivity of the drive when monitoring the output
current to control speed.

The larger the value entered here, the more sensitive the drive is to changes in
the received feedback.

Direct Access Number — F458

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — No

Minimum — 0.0

Maximum — 100.0

Speed Loop Proportional Gain

Program

Feedback

PG Settings

During closed-loop operation, this parameter sets the response sensitivity of the
drive when monitoring the output speed for control.

The larger the value entered here, the larger the change in the output speed for a
given received feedback signal.

Direct Access Number — F460

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — No

Minimum — 1

Maximum — 9999

Speed Loop Stabilization Coefficient

Program

Feedback

PG Settings

During closed-loop operation, this parameter sets the response sensitivity of the
drive when monitoring the output speed for control.

The larger the value entered here, the quicker the response to changes in the
received feedback.

Direct Access Number — F461

Parameter Type — Numerical

Factory Default — 100

Changeable During Run — Yes

Minimum — 1

Maximum — 9999

Load Moment of Inertia 1

Program

Feedback

PG Settings

This parameter is used for calculating accel/decel torque when compensating
for load inertia while operating in the Drooping Control mode.

Direct Access Number — F462

Parameter Type — Numerical

Factory Default — 35

Changeable During Run — Yes

Minimum — 0

Maximum — 100

Second Speed Loop Proportional Gain

Program

Feedback

PG Settings

During closed-loop operation, this parameter sets the sensitivity of the drive
when monitoring the output speed for control.

The larger the value entered here, the more sensitive the drive is to changes in
the received feedback.

Direct Access Number — F463

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — No

Minimum — 1

Maximum — 9999

F453

F463