162

H9 ASD Installation and Operation Manual

RR Input Bias

Program

Frequency

Speed Reference Setpoints

This parameter is used to fine tune the bias of the RR input terminal when this
terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.

This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.

This is accomplished by setting the input source to zero and adjusting this
setting to provide an output of zero from the ASD.

Direct Access Number — F472

Parameter Type — Numerical

Factory Default — 128

Changeable During Run — Yes

Minimum — 0

Maximum — 255

RR Input Gain

Program

Frequency

Speed Reference Setpoints

This parameter is used to fine tune the gain of the RR input terminal when this
terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.

This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.

This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.

Direct Access Number — F473

Parameter Type — Numerical

Factory Default — 154

Changeable During Run — Yes

Minimum — 0

Maximum — 255

RX Input Bias

Program

Frequency

Speed Reference Setpoints

This parameter is used to fine tune the bias of the RX input terminal when this
terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.

This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.

This is accomplished by setting the input source to zero and adjusting this
setting to provide an output of zero from the ASD.

Direct Access Number — F474

Parameter Type — Numerical

Factory Default — 127

Changeable During Run — Yes

Minimum — 0

Maximum — 255

RX Input Gain

Program

Frequency

Speed Reference Setpoints

This parameter is used to fine tune the gain of the RX input terminal when this
terminal is used as the control input while operating in the Speed Control
mode or the Torque Control mode.

This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.

This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.

Direct Access Number — F475

Parameter Type — Numerical

Factory Default — 127

Changeable During Run — Yes

Minimum — 0

Maximum — 255

F472

F475