H9 ASD Installation and Operation Manual

87

Input Terminal Priority

Program

Terminal

Input Special Functions

This parameter is used to allow the Jog and DC Injection Braking input
signals to control the ASD when received via the Terminal Board even though
the system is in the Local mode.

With this parameter enabled, a Jog command or a DC Injection Braking
command received from the Terminal Board will receive priority over
commands from the EOI.

See

F260

for more information on using the Jog function.

See

F250

F252

for more information on DC Injection Braking.

Settings:

0 — Disabled
1 — Enabled

Direct Access Number — F106

Parameter Type — Selection List

Factory Default — Disabled

Changeable During Run — No

16-Bit Binary/BCD Input

Program

Terminal

Input Special Functions

The extended terminal function is used with the optional Expansion IO Card
Option
(P/N ETB004Z).

This parameter defines the format of the binary or BCD data when using the
option card.

Note:

The Expansion IO Card Option 2 option board is required to
use this terminal.

See the Expansion IO Card Option 1 instruction manual (P/N 58685) for
more information on the function of this terminal.

Settings:

0 — None
1 — 12-Bit Binary
2 — 16-Bit Binary
3 — 3-Digit BCD
4 — 4-Digit BCD
5 — Inverted 12-Bit Binary
6 — Inverted 16-Bit Binary
7 — Inverted 3-Digit BCD
8 — Inverted 4-Digit BCD

Selections using 16-bit binary or 4-digit BCD will require the configuration of
terminals S1-S4 on the Terminal Board as binary bits 0 – 3 (

F115

F118

).

The Frequency Mode 1 (

F004

) parameter must be set to Binary/BCD.

For proper scaling of the binary or BCD input, parameters

F228

F231

must

be configured.

Direct Access Number — F107

Parameter Type — Selection List

Factory Default — None

Changeable During Run — No

F106

F107