H9 ASD Installation and Operation Manual

RX Input Point 2 Setting

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control
mode or the Torque Control mode.

This parameter sets the RX input level that is associated with RX Input Point 2
Frequency

when operating in the Speed control mode or is associated with the

RX Input Point 2 Rate when operating in the Torque Control mode.

This value is entered as -100% to +100% of the RX input signal range.

See RX Input Point 1 Setting for more information on this setting when used
for Speed control.

See RX Input Point 1 Rate for more information on this setting when used for
Torque Control.

Direct Access Number — F218

Parameter Type — Numerical

Factory Default — +100

Changeable During Run — Yes

Minimum — -100.0

Maximum — +100.0

Units — %

RX Input Point 2 Frequency

Program

Frequency

Speed Reference Setpoints

This parameter is used to set the gain and bias of the RX input terminal when
the RX terminal is used as the control input while operating in the Speed
Control
mode.

This parameter sets RX Input Point 2 Frequency and is the frequency that is
associated with the setting of RX Input Point 2 Setting when operating in the
Speed Control mode.

See RX Input Point 1 Setting for more information on this setting.

Direct Access Number — F219

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Minimum — 0.00.

Maximum — Max. Freq. (

F011

)

Units — Hz