F016, F017 – Toshiba H9 User Manual

Page 90

Advertising
background image

82

H9 ASD Installation and Operation Manual

Manual Torque Boost 1

Program

Fundamental

Motor Set #1

The Manual Torque Boost 1 function is used to increase the low frequency
torque for high-inertia loads by increasing the output voltage at frequencies
below ½ of the Base Frequency 1 (

F014

) setting.

The value programmed as a boost percentage establishes an output voltage vs.
output frequency relationship to be used to start the motor or to provide
smoother operation.

Note:

Setting an excessive Torque Boost level may cause nuisance
tripping and mechanical stress to loads.

Direct Access Number — F016

Parameter Type — Numerical

Factory Default — (ASD-dependent)

Changeable During Run — Yes

Minimum — 0.0

Maximum — 30.0

Units — %

Motor Overload Protection Configuration

Program

Protection

Overload

This parameter is used to protect the motor from an overcurrent condition. The
type of motor being used and the Overload/Stall setting is selected here to
better match the application.

This parameter setting may extend the Overvoltage Stall time settings.

This parameter may be affected by the setting of the Power Running Stall
Continuous Trip Detection Time
(

F452

).

Settings:

0 — Overload Trip without Stall
1 — Overload Trip with Stall
2 — No Overload without Stall
3 — Stall Only
4 — V/f Motor-Overload without Stall
5 — V/f Motor-Overload with Stall
6 — V/f Motor-No Overload without Stall
7 — V/f Motor-Stall Only

Direct Access Number — F017

Parameter Type — Selection List

Factory Default — O/L Trip No Stall

Changeable During Run — Yes

F016

F017