148

H9 ASD Installation and Operation Manual

PID Feedback Signal

Program

Feedback

Feedback Settings

This parameter Enables/Disables PID feedback control. When enabled, this
parameter determines the source of the motor-control feedback.

Settings:

0 — PID Control Disabled
1 — V/I
2 — RR
3 — RX
4 — RX2 Option (AI1)
5 — Option V/I
6 — PG Feedback Option

Proportional-Integral-Derivative (PID) — A closed-loop control technique
that seeks error minimization by reacting to three values: One that is
proportional to the error, one that is representative of the error, and one that is
representative of the rate of change of the error.

Direct Access Number — F360

Parameter Type — Selection List

Factory Default — PID Control
Disabled

Changeable During Run — Yes

PID Feedback Delay Filter

Program

Feedback

Feedback Settings

This parameter determines the delay in the ASD output response to the motor-
control feedback signal (signal source is selected at

F360

).

Direct Access Number — F361

Parameter Type — Numerical

Factory Default — 0.1

Changeable During Run — Yes

Minimum — 0.0

Maximum — 25.0

PID Feedback Proportional (P) Gain

Program

Feedback

Feedback Settings

This parameter determines the degree that the Proportional function affects the
output signal. The larger the value entered here, the quicker the drive responds
to changes in feedback.

Direct Access Number — F362

Parameter Type — Numerical

Factory Default — 0.10

Changeable During Run — Yes

Minimum — 0.01

Maximum — 100.0

PID Feedback Integral (I) Gain

Program

Feedback

Feedback Settings

This parameter determines the degree that the Integral function affects the
output signal. The smaller the value here, the more pronounced the effect of the
integral function on the output signal.

Direct Access Number — F363

Parameter Type — Numerical

Factory Default — 0.10

Changeable During Run — Yes

Minimum — 0.01

Maximum — 100.00

PID Deviation Upper Limit

Program

Feedback

Feedback Settings

This parameter determines the maximum amount that the feedback may
increase the output signal.

Direct Access Number — F364

Parameter Type — Numerical

Factory Default — 60.00

Changeable During Run — Yes

Minimum — 0.00

Maximum — 60.00

Units — Hz