Viewing trip information, Trip history, Trip record at monitor screen – Toshiba H9 User Manual

Page 263: Clearing a trip, Viewing trip information clearing a trip

Advertising
background image

H9 ASD Installation and Operation Manual

255

Viewing Trip Information

In the event that the condition causing an Alarm does not return to the normal operating level within a
specified time, the H9 ASD Faults and a Trip is incurred.

When a trip occurs, the resultant error information may be viewed either from the

Trip History

screen

(Program

⇒ Utilities ⇒ Trip History) or from the Monitor screen.

Trip History

The Trip History screen records the system parameters for up to 20 trips. The recorded trips are
numbered from zero to 19. Once the Trip History record reaches trip number 19, the oldest recorded trip
will be deleted with each new record stored (first-in first-out). The Trip # field may be selected and
scrolled through to view the recorded trip information for a given trip number. The monitored parameters
are listed in

Table 15

as At-trip Recorded Parameters (parameter readings at the time that the trip

occurred).

Table 15. Trip History Record Parameters.

Trip Record at Monitor Screen

The at-trip condition of the last 4 incurred trips may be viewed at the Monitor Screen. The Monitor
Screen
displays the records of up to four trips and catalogs each trip as Past Trip #1 through Past Trip #4
(see

pg. 43

). Once reset (Type Reset), the trip records are erased. If no trips have occurred since being

powered up or since the last reset, None is displayed for each trip record.

The Monitor Screen at-trip record is erased when the H9 ASD is reset.

Note:

An improper H9 ASD setup may cause some trips — reset the ASD to the Factory
Default
settings before pursuing a systemic malfunction (Program

Utilities Type

Reset

Reset to Factory Settings).

Clearing a Trip

Once the cause of the trip has been corrected, performing a

Reset

re-enables the H9 ASD for normal

operation.

The record of a trip may also be cleared using either of the following methods:

• Cycling power (trip info may be saved via

F602

if desired),

• Pressing the Stop|Reset key twice,

• Remotely via the communications channel,

• Momentarily connecting terminal RES to CC of the Terminal Board, or

• Via Program

⇒ Utilities ⇒ Type Reset ⇒ Clear Past Trip (clears Monitor Screen records only).

At-trip Recorded Parameters

1) Trip Number

8) Frequency Reference

15) Feedback (1 sec.)

22) ASD Overload

2) Trip Type

9) Bus Voltage

16) Torque

23) DBR Overload

3) Time and Date

10) Discrete Input Status

17) Torque Reference

24) Motor Load

4) Frequency at Trip

11) OUT1/OUT2/FL Status

18) Torque Current

25) ASD Load

5) Output Current

12) Timer

19) Excitation Current

26) DBR Load

6) Output Voltage

13) Post Compensation Frequency

20) PID Value

27) Input Power

7) Direction

14) Feedback (inst.)

21) Motor Overload

28) Output Power

Trip records are comprised of the full list of monitored parameters (28).