Preset Speed 1

Program

Frequency

Preset Speeds

Up to 15 output frequency values that fall within the Lower Limit and the
Upper Limit range may be programmed into the drive and output as a Preset
Speed
. This parameter assigns an output frequency to binary number 0001 and
is identified as Preset Speed #1. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed.

Perform the following setup to allow the system to receive Preset Speed
control input at the S1 – S4 terminals:

1.

Program

⇒ Fundamental ⇒ Standard Mode Selection ⇒ Command Mode

Terminal Block.

2.

Program

⇒ Terminal ⇒ Input Terminals ⇒ S1 (set to Preset Speed

Command 1; LSB of 4-bit count). Repeat for S2S4 (MSB of 4-bit count)
as Preset Speed Command 24, respectively (all Normally Open).

3.

Program

⇒ Frequency ⇒ Preset Speeds ⇒ Preset Speed 1 (set an output

frequency as Preset Speed #1; repeat for Preset Speeds 2 15 as
required).

4.

Program

⇒ Pattern Run ⇒ Operation Mode ⇒ Preset Speed Operation

Mode.

Select Enabled to use the direction, accel/decel, and torque settings of the
Preset Speed being run. The torque settings used will be as defined in

F170

F181

and as selected via the associated discrete input terminals V/f

Switching 1 and 2 in

Table 5 on pg. 236

.

Select Disabled to use the speed setting only of the Preset Speed being run.

5.

Place the system in the Remote mode (Local|Remote LED Off).

6.

Provide a Run command (connect F and/or R to CC).

Connect S1 to CC to run Preset Speed #1 (S1 to CC = 0001 binary).

With S1S4 configured to output Preset Speeds (

F115

F118

), 0001 – 1111

may be applied to S1 – S4 of the Terminal Board to run the associated Preset
Speed
. If bidirectional operation is required, F and R must be connected to CC,
and Preset Speed Operation Mode must be set to Enabled at

F560

.

With S1 being the least significant bit of a binary count, the S1 – S4 settings
will produce the programmed speed settings as indicated in the Preset Speed
Truth Table
to the right.

Preset Speeds are also used in the Pattern Run mode.

Direct Access Number — F018

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — Lower Limit (

F013

)

Maximum — Upper Limit (

F012

)

Units — Hz

Preset Speed Truth Table

Preset Speed 2

Program

Frequency

Preset Speeds

This parameter assigns an output frequency to binary number 0010 and is
identified as Preset Speed #2. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see

F018

for more information on

this parameter).

Direct Access Number — F019

Parameter Type — Numerical

Factory Default — 0.0

Changeable During Run — Yes

Minimum — Lower Limit (

F013

)

Maximum — Upper Limit (

F012

)

Units — Hz

Preset Speed 1

Preset

S4

MSB

S3

S2

S1

LSB

Output

1

0

0

0

1

F018

2

0

0

1

0

F019

3

0

0

1

1

F020

4

0

1

0

0

F021

5

0

1

0

1

F022

6

0

1

1

0

F023

7

0

1

1

1

F024

8

1

0

0

0

F287

9

1

0

0

1

F288

10

1

0

1

0

F289

11

1

0

1

1

F290

12

1

1

0

0

F291

13

1

1

0

1

F292

14

1

1

1

0

F293

15

1

1

1

1

F294

Note: 1 = Terminal connected to CC.