Preset Speed 15

Program

Frequency

Preset Speeds

This parameter assigns an output frequency to binary number 1111 and is
identified as Preset Speed #15. The binary number is applied to S1S4 of the
Terminal Board to output the Preset Speed (see

F018

for more information on

this parameter).

Direct Access Number — F294

Parameter Type — Numerical

Factory Default — 0.00

Changeable During Run — Yes

Minimum — Lower Limit (

F013

)

Maximum — Upper Limit (

F012

)

Units — Hz

PWM Carrier Frequency

Program

Special

Carrier Frequency

This parameter sets the frequency of the pulse width modulation signal applied
to the motor.

Note:

When operating in the Vector Control mode the carrier
frequency should be set to 2.2 kHz or above

.

Note:

If the PWM carrier frequency is set at 2.0 kHz or above, it cannot
be decreased below 2.0 kHz while running. If the PWM carrier
frequency is set at 1.9 kHz or below, it cannot be increased above
2.0 kHz while running. Either change requires that the ASD be
stopped and restarted for the changes to take effect.

Direct Access Number — F300

Parameter Type — Numerical

Factory Default — 2.200

Changeable During Run — No

Minimum — 1.0

Maximum — (ASD-dependent)

Units — kHz

Auto Restart Selection

Program

Protection

Retry/Restart

This parameter Enables/Disables the ability of the drive to start into a spinning
motor when the STCC connection opens momentarily and is then closed
(Break/Make ST) or after a power interruption (momentary power failure).

Settings:

0 — Off
1 — Enabled (at Power Failure)
2 — Enabled (at Make-Break ST-CC)
3 — Enabled (at Make-Break ST-CC or Power Failure)
4 — Enabled (at Run)

Direct Access Number — F301

Parameter Type — Selection List

Factory Default — Off

Changeable During Run — No

F294