Regenerative Power Ridethrough Mode

Program

Protection

Undervoltage/Ridethrough

This parameter determines the motor-control response of the drive in the event
of a momentary power outage or undervoltage condition.

During a Ridethrough, regenerative energy is used to maintain the control
circuitry settings for the duration of the Ridethrough; it is not used to drive the
motor. The motor(s) of the system are stopped and then restarted automatically
if so configured.

In a multiple-motor application, there will be a requirement to synchronize the
stopping and restarting of the motors as not to cause breakage in the product
being processed by the motors stopping/starting at different times (e.g., wire
spools, bobbin winder for textile machines, etc.). Parameters

F317

and

F318

must be setup to synchronize motor operation as to avoid breakage in these
types of applications.

Note:

If used to restart the motors, the Retry setup of

F301

is required.

Note:

The Jog function will not operate while in the Synchronized
Decel/Accel
mode.

Settings:

0 — Off
1 — Ridethrough On
2 — Decel Stop (during power failure)
3 — Synchronized ACC/DEC (TB)
4 — Synchronized ACC/DEC (TB + Power Off)

Ridethrough Setup Requirements

1.

Select the Ridethrough Mode at

F302

.

2.

Select the Ridethrough Time at

F310

.

3.

Select the Synchronized Stop/Start Times at

F317

/

F318

(if required).

Note:

F317

and

F318

are not functional while operating in the Torque

or Position control modes, or for the Jog Run function (

F260

).

4.

Set a discrete input terminal to Power Failure Synchronized Signal and
activate the terminal to enable the Synchronized Accel/Decel function.

5.

Select the Ridethrough Control Level at

F629

.

Direct Access Number — F302

Parameter Type — Selection List

Factory Default — Off

Changeable During Run — Yes

F302