H9 ASD Installation and Operation Manual

Input Terminal 4 (RES) Response Time

Program

Terminal

Input Terminal Delays

This parameter delays the response of the drive to any change in the RES
terminal input by the programmed value (see waveforms at

F140

).

The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.

Direct Access Number — F143

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Input Terminal 5 – 12 Response Time

Program

Terminal

Input Terminal Delays

This parameter delays the response of the drive to any change in the 5 – 12
terminal inputs by the programmed value (see waveforms at

F140

).

The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.

Direct Access Number — F144

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Input Terminal 13 – 20 Response Time

Program

Terminal

Input Terminal Delays

This parameter delays the response of the drive to any change in the 13 – 20
terminal inputs by the programmed value (see waveforms at

F140

).

The delay may be increased to provide additional electrical noise immunity or
to prevent the ASD from responding to contact bounce or chatter.

Direct Access Number — F145

Parameter Type — Numerical

Factory Default — 8.0

Changeable During Run — No

Minimum — 2.0

Maximum — 200.0

Units — mS

Input Terminal 17 (B12) Function

Program

Terminal

Input Terminals

This parameter is used to set the functionality of the B12 discrete input
terminal.

In addition, this input terminal must be specified as Normally Open or
Normally Closed.

This setting assigns the functionality of the programmable B12 terminal to any
one of the user-selectable functions listed in

Table 5 on pg. 236

.

See the My Function Instruction Manual (P/N 58692) for more information
on the function of this terminal.

Direct Access Number — F164

Parameter Type — Selection List

Factory Default — Unassigned

Changeable During Run — No

Input Terminal 18 (B13) Function

Program

Terminal

Input Terminals

This parameter is used to set the functionality of the B13 discrete input
terminal.

In addition, this input terminal must be specified as Normally Open or
Normally Closed.

This setting assigns the function of the programmable B13 terminal to any one
of the user-selectable functions listed in

Table 5 on pg. 236

.

See the My Function Instruction Manual (P/N 58692) for more information
on the function of this terminal.

Direct Access Number — F165

Parameter Type — Selection List

Factory Default — Unassigned

Changeable During Run — No

F143

F165