Configuration – Lenze ECSCSxxx User Manual

Page 172

Advertising
background image

Configuration

Configuring MotionBus/system bus (CAN)
Setting CAN node address and baud rate

8

l

172

EDBCSXS064 EN 4.0

8.1.1.2

Settings via codes

)

Note!

ƒ

The settings in C0350 (CAN node address) and C0351 (baud rate) are only
used if the (address) switches 2 ... 7 of the DIP switch S1 are switched off
(OFF).

ƒ

If only one (address) switch 2 ... 7 is switched on (ON), the settings of the DIP
switch S1 usually apply.

ƒ

The baud rate (C0351) must be set identically for all CAN bus nodes.

ƒ

If the Lenze setting has been loaded via C0002,
– C0351 is set to 0 (500 kbit/s);
– you have to reset the baud rate (C0351) and the CAN node address

(C0350).

Code

Possible settings

IMPORTANT

No.

Designation

Lenze/
{Appl.}

Selection

C0350 CAN address

32

Node address for CAN bus
interface X4

l

This code is not active if one
of the switches 2 ... 7 of the
DIP switch is set to "ON".
(

^ 169)

l

After the setting process, a
reset node is required.

l

A definite node address must
be assigned to each CAN
node.

^ 169

^ 460

1

{1}

63

C0351 CAN baud rate

0

Baud rate for CAN bus interface
X4

l

The baud rate must be set
identically for all CAN nodes.

l

This code is not active if one
of the switches 2 ... 7 of the
DIP switch is set to "ON".

l

After the setting process, a
reset node is required.

^ 169

0

500 kbps

1

250 kbits/sec

2

125 kbit/s

3

50 kbps

4

1000 kbit/s

Save changes with C0003 = 1.

The settings are only accepted after carrying out one of the following actions:

ƒ

Renewed switch−on of the 24 V low−voltage supply

ƒ

Reset node via the bus system (by the network management (NMT))

ƒ

Reset node with C0358 = 1

)

Note!

If reset node is executed via GDC, communication will be interrupted. You
therefore have to log in again manually or find the devices connected to the
bus once again (fieldbus scan).